Built-in with isolation transformer, VL series Solar TX purifies input power to connected devices. It can be operated in three different operation modes, on-grid, off-grid and grid-tie with backup, depending on power requirements. InfiniSolar TX is a flexible and smart hybrid inverter which utilizes solar power, AC utility, and battery power source to supply continuous power. Besides, it can set power usage priority as self-consumption for maximizing your benefit.
MODEL | VL series Solar TX-20KW | |
Maximum PV Input Power | 30KW | |
Rated Output Power | 20KW | |
Maximum Charging Power | 20KW | |
GRID-TIE OPERATION | ||
PV INPUT (DC) | ||
Nominal DC Voltage / Maximum DC Voltage | 720 VDC / 950 VDC | |
Start-up Voltage / Initial Feeding Voltage | 500 VDC / 550 VDC | |
MPPT Voltage Range | 550 VDC ~ 900 VDC | |
Number of MPP Trackers/Max. Input Current | 1/48 Amp | |
Full power MPP Voltage Range | 625 VDC ~ 900 VDC | |
GRID OUTPUT (AC) | ||
Output Frequency Range | 47.5 ~ 51.5 Hz or 59.3 ~ 60.5 Hz | |
Nominal Output Voltage | 230 VAC (P-N) / 400 VAC (P-P) | |
Output Voltage Range | 184 – 265 VAC per phase | |
Nominal Output Current | 29 A per phase | |
Power Factor | > 0.99 | |
EFFICIENCY | ||
Maximum Conversion Efficiency (DC/AC) | 91% | |
OFF-GRID OPERATION | ||
AC INPUT | ||
AC Start-up Voltage / Auto Restart Voltage | 120-140 VAC per phase / 180 VAC per phase | |
Acceptable Input Voltage Range | 170 – 280 VAC per phase | |
Maximum AC Input Current | 40 A per phase | |
PV INPUT (DC) | ||
Maximum DC Power / Maximum DC Voltage | 30KW / 950 vdc | |
MPPT Voltage Range | 550 VDC ~ 900 VDC | |
Number of MPP Trackers/Max. Input Current | 1/48 Amp | |
BATTERY MODE OUTPUT (AC) | ||
Nominal Output Voltage | 230 VAC (P-N) / 400 VAC (P-P) | |
Output Waveform | Pure sine wave | |
Efficiency (DC to AC) | >91% | |
HYBRID OPERATION | ||
PV INPUT (DC) | ||
Nominal DC Voltage / Maximum DC Voltage | 720 VDC / 950 VDC | |
Start-up Voltage / Initial Feeding Voltage | 500 VDC / 550 VDC | |
MPPT Voltage Range | 550 VDC ~ 900 VDC | |
Number of MPP Trackers/Max. Input Current | 1/48 Amp | |
GRID OUTPUT (AC) | ||
Nominal Output Current | 29 A per phase | |
Nominal Output Voltage | 230 VAC (P-N) / 400 VAC (P-P) | |
Output Frequency Range | 47.5 ~ 51.5 Hz or 59.3 ~ 60.5 Hz | |
Output Voltage Range | 184 – 265 VAC per phase | |
Power Factor | > 0.99 | |
AC INPUT | ||
AC Start-up Voltage / Auto Restart Voltage | 120-140 VAC per phase / 180 VAC per phase | |
Acceptable Input Voltage Range | 170 – 280 VAC per phase | |
Maximum AC Input Current | 40.0 A per phase | |
BATTERY MODE OUTPUT (AC) | ||
Nominal Output Voltage | 230 VAC (P-N) / 400 VAC (P-P) | |
Efficiency (DC to AC) | >91% | |
BATTERY & CHARGER | ||
Nominal Battery Voltage | 384 VDC | |
Maximum Charging Current | 50A | |
GENERAL | ||
PHYSICAL | ||
Dimension, D X W X H (mm) | 559 x 320 x 909 | |
Net Weight (kgs) | 120 | |
INTERFACE | ||
Communication Port | RS-232/USB | |
Intelligent Slot | Optional SNMP, GRPS, WIFI, Modbus cards available | |
ENVIRONMENT | ||
Humidity | 0 ~ 90% RH (No condensing) | |
Operating Temperature | -10 to 55°C | |
Altitude | 0 ~ 1000 m** |