VL series Solar VII is upgrade version for our VL series Solar V first generation. This second generation inverter can accept high PV voltage range and this feature will facilitate PV system installation. Besides, battery independency feature will keep inverter running no matter battery is connected or not. We also offers parallel operation function up to 9 units for 2KW, 3KW, 5KW and 6KW. It offers high flexibility for future power expansion.
MODEL | VL series Solar V II 1.5KW | VL series Solar V II 2KW | VL series Solar V II 3KW-24V | VL series Solar V II 3KW-48V | VL series Solar V II 5KW | VL series Solar V II 6KW | |
PHASE | 1-phase in / 1-phase out | ||||||
Maximum PV Input Power | 2000W | 3000W | 4000W | 5000W | 6000W | ||
Rated Output Power | 1500W | 2000W | 3000W | 5000W | 6000W | ||
Maximum Charging Power | 2000W | 2880W | 1440W | 2880W | 5000W | ||
GRID-TIE OPERATION | |||||||
PV INPUT (DC) | |||||||
Nominal DC Voltage / Maximum DC Voltage | 120 VDC / 400 VDC | 240 VDC / 450 VDC | 360 VDC / 450 VDC | 360 VDC / 500 VDC | |||
Start-up Voltage / Initial Feeding Voltage | 130VDC / 150 VDC | ||||||
MPP Voltage Range | 120 VDC ~ 380 VDC | 90 VDC ~ 430 VDC | 120 VDC ~ 430 VDC | ||||
Number of MPP Trackers / Maximum Input Current | 1 / 18 A | 1 / 18A | 1 / 27A | ||||
GRID OUTPUT (AC) | |||||||
Nominal Output Voltage | 220/230/240 VAC | ||||||
Output Voltage Range | 184-264.5 VAC or 195.5-253 VAC (Selectable) | ||||||
Nominal Output Current | 6.5A | 8.7A | 13A | 21.7A | 26A | ||
Power Factor | > 0.99 | ||||||
EFFICIENCY | |||||||
Maximum Conversion Efficiency (DC/AC) | 95% | ||||||
OFF-GRID OPERATION | |||||||
AC INPUT | |||||||
AC Start-up Voltage / Auto Restart Voltage | 120 – 140 VAC / 180 VAC | ||||||
Acceptable Input Voltage Range | 90 – 280 VAC or 170 – 280 VAC | ||||||
Maximum AC Input Current | 30 A | 40 A | |||||
Frequency Range | 50 Hz/60 Hz (Auto sensing) | ||||||
PV INPUT (DC) | |||||||
Maximum DC Voltage | 400 VDC | 450 VDC | 500 VDC | ||||
MPP Voltage Range | 120 VDC ~ 380 VDC | 90 VDC ~ 430 VDC | 120 VDC ~ 430 VDC | ||||
Number of MPP Trackers / Maximum Input Current | 1 / 18 A | 1 / 18A | 1 / 27A | ||||
BATTERY MODE OUTPUT (AC) | |||||||
Nominal Output Voltage | 220/230/240 VAC | ||||||
Output Waveform | Pure sine wave | ||||||
Efficiency (DC to AC) | 93% | ||||||
HYBRID OPERATION | |||||||
PV INPUT (DC) | |||||||
Nominal DC Voltage / Maximum DC Voltage | 120 VDC / 400 VDC | 240 VDC / 450 VDC | 360 VDC / 450 VDC | 360 VDC / 500 VDC | |||
Start-up Voltage / Initial Feeding Voltage | 130VDC / 150 VDC | ||||||
MPP Voltage Range | 120 VDC ~ 380 VDC | 90 VDC ~ 430 VDC | 120 VDC ~ 430 VDC | ||||
Number of MPP Trackers / Maximum Input Current | 1 / 18 A | 1 / 18A | 1 / 27A | ||||
GRID OUTPUT (AC) | |||||||
Nominal Output Current | 6.5A | 8.7A | 13A | 21.7A | 26A | ||
Nominal Output Voltage | 220/230/240 VAC | ||||||
Output Voltage Range | 184 – 264.5 VAC or 195.5 – 253 VAC (Selectable) | ||||||
BATTERY MODE OUTPUT (AC) | |||||||
Nominal Output Voltage | 220/230/240 VAC | ||||||
Efficiency (DC to AC) | 93% | ||||||
Output Waveform | Pure sine wave | ||||||
BATTERY & CHARGER | |||||||
Nominal DC Voltage | 48 VDC | 24 VDC | 48 VDC | ||||
Maximum Charging Current | 40A | 60 A | 100 A | 120 A | |||
Maximum Solar Charging Current | 30A | 60 A | 100 A | 120 A | |||
Maximum AC Charging Current | 40A | 60 A | 100 A | 120 A | |||
GENERAL | |||||||
PHYSICAL | |||||||
Dimension, D X W X H (mm) | 100 x 300 x 440 | 120 x 295 x 468 | |||||
Net Weight (kgs) | 8 | 11 | 12 | ||||
INTERFACE | |||||||
Communication Port | USB or RS-232/Dry Contact | ||||||
Parallel Function | N/A | Yes, 9 units | |||||
ENVIRONMENT | |||||||
Operating Humidity | 0 ~ 90% RH (No condensing) | ||||||
Operating Temperature | -10°C to 50°C |